Nader
NDZ3AT-150R Series DC Contactor, Nader
Model: NDZ3AT-150R
Key specifications
- Rated current In (A) 150A
- Rated working voltage Ue DC12~1000V
- Coil control voltage Uc (V) DC12V/24V
Technical parameters
Main Circuit Polarity | None | |
Main Contact Form | 1NO | |
Operational Voltage Range | DC12~1000V | |
Rated current (A) | 150A | |
Contact Resistance | ≤0.5mΩ(at 150A) | |
Short-circuit withstand current | 2000A 600ms、1200A 1s、300A 1min、200A 10min、150A continuous | |
Control Coil(20°C) | Rated voltage Ui (V) | DC12V, DC24V |
Coil Polarity | Polarized | |
Coil Power Consumption | Pick-up: 26W; Hold: 3W | |
Auxiliary Contact | Type | None, 1NO |
Rated Current/Voltage | 2A/DC24V | |
Minimum Makeable Load | 100mA/6V | |
Maximum breaking current | DC320V 2000A | Once |
Insulation resistance | 1000mΩ, DC1000V | |
Dielectric Strength | AC3300V 60s (leakage current ≤1mA) | |
Installation position torque | M5 screw(3~4N.m) | |
Wiring terminal torque | M6 screw(6~8N.m) | |
Certificates | CCC、CB、CE、TUV | |
Mechanical life | 200000 times, frequency 3600 times/h | |
Electrical life | DC1000V 150A 1000times | |
Shock Stability | 20g | |
Shock Resistance | 50g | |
Vibration Resistance | 10~500Hz | |
Weight | Approx. 400g | |
Normal Working Environment | ·Operating environment:-40~85℃ ·Operating humidity:5%~95% ·Pollution level:3 | |
Installation Mode | Screw mounting | |
Environmental Compliance | Comply with the RoHS directives | |