Nader
NDZ3T-400 Series DC Contactor, Nader
Model: NDZ3T-400
Key specifications
- Rated current In (A) 400A
- Rated working voltage Ue DC750V
- Coil control voltage Uc (V) DC12V/24/48V
Technical parameters
Rated current (A) | 400A | |
Rated voltage Ue (V) | DC750V | |
Main Circuit Polarity | Polarized | |
Insulation voltage Ui (V) | DC1000V | |
Control Coil | Rated voltage Ui (V) | DC12V, DC24V, DC48V |
Operating Voltage | 75%~110% Uc | |
Drop-out Voltage | 10%~60% Uc | |
Coil Polarity | Polarized | |
Turn-on Time (20°C, Rated Voltage) | ≤30ms | |
Turn-off Time (20°C) | ≤10ms | |
Coil Power Consumption (20°C) | Pick-up: 45W; Hold: 4.5W | |
Installation position torque | M5 screw(3~4N.m) | |
Wiring terminal torque | M6 screw(6~8N.m) | |
Certificates | CCC, CE, CB, TUV, UL | |
Mechanical life | 200000 times, frequency 3600 times/h | |
Electrical life (Make 0.6s/Break 5.4s, Resistive Load) | DC750V 400A | 1000 times |
DC500V 400A | 3000 times | |
DC500V 400A | 1000 times | |
Maximum breaking current | DC750V 4000A | once |
Short-circuit withstand current | 10Ie 600ms | |
Contact Resistance (at Rated Current) | ≤0.2mΩ | |
Insulation resistance | 1000mΩ, DC1000V | |
Dielectric Strength | AC3000V 60s (leakage current ≤1mA) | |
Shock Resistance | ·Stability: 20g (ON state), 10g (OFF state) (half-sine pulse: 11ms, detection time 10μs) ·Destruction: 50g (half-sine pulse: 6ms) | |
Vibration Resistance | 10~500Hz 5g | |
Normal Working Environment | ·Operating environment:-40~85℃ ·Operating humidity:5%~95% ·Pollution level:3 ·Protection class:IP67(Except the connecting terminals) ·Installation direction:Vertical installation | |
Installation Mode | Screw mounting | |
Environmental Compliance | Comply with the RoHS directives | |