Nader

NDB1-125 Series AC/DC MCB, Nader

Model: NDB1-125

Key specifications

  • Rated current In (A) 50A, 63A, 80A, 100A, 125A
  • Rated voltage Ue (V) AC230/240/400/415V, DC60/80/125V
  • Poles 1P, 2P, 3P, 4P
  • Breaking capacity (Icu) 5kA, 10kA

Technical parameters

Rated voltage (Ue)

AC230/240(1P), AC400/415 (2P、3P、4P), DC60/80 (1P), DC80/125 (2P)

Rated current (In)

50A, 63A, 80A, 100A, 125A

Tripping Characteristic

C:8 (1±20%)In, D:12 (1±20%)In

Tripping curve

C Curve, D Curve

Rated breaking capacity (Icn)

CCC、CB、CE、TUV:10kA, UL1077: 5kA: U1; 10kA: U2

Rated Ultimate Short-Circuit Breaking Capacity (Icu)

CCC、CB、CE、TUV:10kA, UL1077: 5kA: U1; 10kA: U2

Rated Service Short-Circuit Breaking Capacity (Ics)

CCC、CB、CE、TUV:7.5kA, UL1077: 5kA: U1; 10kA: U2

Number of Poles

1P、2P、3P、4P

Standards and Certificates

·CCC、CB、CE、TUV、UL1077 (D125 has no UL1077 certification)

·GB/T 14048.2, IEC 60947-2

Environmental Requirements

RoHS

Rated Insulation Voltage

500V

Rated Impulse Withstand Voltage

4kV

Rated Frequency

50/60Hz

Wiring

·Adopt tunnel type wiring

·Connection capability: 10mm2 to 50 mm2

·Connection screw M7,Twisting moment 3.5N.m

Mechanical Life

15000 times

Electrical Life

6000 times

Working Condition

·Ambient temperature: -40℃~+70℃

·Storage temperature: -40℃~+80℃

·Relative air humidity≤95%

·Altitude: ≤2000m

·Pollution degree: 3

·Used in place without obvious shock and vibration

·Protection Degree: IP20

Isolation function

·Indication of real breaking

·Green color in the indication window indicates the contacts are open.